SHIQing-lin,JIANGHong-guang.Cause Analysis and Reinforcement of the Floating Accident in a Clear Water Tank in Pumping Station[J].China Water & Wastewater,2022,38(14):106-111.
Cause Analysis and Reinforcement of the Floating Accident in a Clear Water Tank in Pumping Station
China Water & Wastewater[ISSN:1000-4062/CN:12-1073/TU]
volume:
第38卷
Number:
第14期
Page:
106-111
Column:
Date of publication:
2022-07-17
- Abstract:
- Taking the floating accident in a clear water tank of a pump station as an example, the causes of the accident are deeply analyzed and studied from the aspects of survey, design, construction and use, especially in combination with the various processes and details in the construction process. The methods of increasing the cross-section of components, sticking carbon fiber cloth, adding protective layer, grouting chemical of cracks and improving the drainage system of foundation pit are proposed. The structural reinforcement methods and repair measures after the floating of clear water tank are summarized. At the same time, the anti-floating design and construction precautions of clear water tank structure are put forward. Years of practice shows that reinforced tank has been operating normally and withstood the test of various extreme weather, which can provide some reference for the prevention and treatment of similar accidents.
Last Update: