KOU Dian liang,YUAN Jian ping,CHEN Xue mei.Application of High-pressure Water Mist Fire Extinguishing System in Utility Tunnel[J].China Water & Wastewater,2018,34(20):72-75.
高压细水雾灭火系统在综合管廊中的应用
- Title:
- Application of High-pressure Water Mist Fire Extinguishing System in Utility Tunnel
- 文章编号:
- 1000-4602(2018)20-0072-04
- Keywords:
- highpressure water mist fire extinguishing system; utility tunnel; automatic fire extinguishing system
- 分类号:
- TU892
- 文献标志码:
- C
- 摘要:
- 现行的细水雾灭火系统技术规范中,要求开式系统的防护区数量不应大于3个,单个防护区容积不宜大于3 000 m3。由于综合管廊的狭长特殊空间结构,这些条文不利于高压细水雾灭火系统应用在管廊中。在南宁市玉洞大道南北侧道路综合管廊设计中,采用了高压细水雾消防系统。设计参考重庆市地方标准及档案行业标准并做出如下优化,取消防护区数量3个的限制;单个防护区的容积按不大于3 000 m3控制;单个分区控制阀的控制面积按120~150 m2控制。优化后的设计方案更符合综合管廊消防的特点,投资更省。
- Abstract:
- According to the current technical specification for water mist fire extinguishing system, the number of open protection zones is no more than 3 and the volume of single protection zone is no more than 3 000 m3 in open type system. However due to the narrow and special spatial structure of the utility tunnel, these requirements are not conductive to the application of high pressure water mist fire extinguishing system in utility tunnel. The high pressure water mist fire extinguishing system was used in the design of the utility tunnel on the South and North side of Yudong Road in Nanning. Based on local standards of Chongqing City and archives industry standards, there are some improvements in the design process: ①canceling limitation of 3 enclosures;②controlling the volume of a single protective area no more than 3 000 m3; ③determining the area of controlled valve in single section as 120-150 m2. The optimized design made investment more economical and it was more in line with the characteristics of fire extinguishing in the utility tunnel.
参考文献/References:
[1]吴平,栗心国.细水雾灭火系统在档案馆中的设计优化探讨[J]. 给水排水,2016,42(10):100-103.Wu Ping,Li Xinguo. Probe into design optimization for the water mist system in archives[J]. Water & Wastewater Engineering,2016,42(10):100-103(in Chinese).
[2]李露.高压细水雾灭火系统在档案馆中的应用[J]. 给水排水,2016,42(4):95-98.Li Lu. Application of high pressure water mist fire extinguishing system in archives[J]. Water & Wastewater Engineering,2016,42(4):95-98(in Chinese).
[3]涂小华,欧阳开. 广州地铁七号线高压细水雾灭火系统的设计[J]. 中国给水排水,2015,31(14):43-45,49.Tu Xiaohua,Ouyang Kai. Design of high pressure water mist fire extinguishing system in Guangzhou Metro Line No.7[J]. China Water & Wastewater,2015,31(14):43-45,49(in Chinese).
相似文献/References:
[1]曹益宁,董永红.城市综合管廊入廊污水管道及重要节点的设计[J].中国给水排水,2018,34(20):67.
CAO Yi ning,DONG Yong hong.Design of Sewage Pipe and Important Nodes of Urban Utility Tunnel[J].China Water & Wastewater,2018,34(20):67.
[2]强健.综合管廊的功能区间及应用[J].中国给水排水,2020,36(18):45.
QIANG Jian.Functional Section in the Utility Tunnel and Its Application[J].China Water & Wastewater,2020,36(20):45.
[3]张晏晏,曹伟新,陆继诚,等.综合管廊超细干粉自动灭火系统设计探讨[J].中国给水排水,2020,36(22):136.
ZHANG Yan-yan,CAO Wei-xin,LU Ji-cheng,et al.Discussion on Design of Ultra-fine Dry Powder Automatic Fire Extinguishing System in Utility Tunnel[J].China Water & Wastewater,2020,36(20):136.
[4]唐兰,张月,王长祥.保障全周期本质安全的综合管廊规划编制方法及要求[J].中国给水排水,2020,36(24):60.
TANG Lan,ZHANG Yue,WANG Chang-xiang.Planning Compilation Methods and Technical Requirements for Utility Tunnel to Ensure Intrinsic Safety throughout the Life Cycle[J].China Water & Wastewater,2020,36(20):60.
[5]赫明水,王长祥,吕杨,等.城市综合管廊真空排水系统模型试验及设计技术研究[J].中国给水排水,2020,36(24):66.
HE Ming-shui,WANG Chang-xiang,L?Yang,et al.Research on Model Test and Design Technology about the Vacuum Drainage System of Utility Tunnel[J].China Water & Wastewater,2020,36(20):66.
[6]尚琳,刘远,何发龙,等.考虑人员安全疏散的综合管廊防火分区设计长度研究[J].中国给水排水,2020,36(24):72.
SHANG Lin,LIU Yuan,HE Fa-long,et al.Study on the Utility Tunnel Fire Compartment Design Length Considering Safe Evacuation[J].China Water & Wastewater,2020,36(20):72.
[7]许云骅,金善朝,徐浩煜.综合管廊运维目标、原则及新技术应用[J].中国给水排水,2021,37(8):53.
XU Yun-hua,JIN Shan-chao,XU Hao-yu.Targets, Principles and New Technologies Application of the Utility Tunnel Operation and Maintenance[J].China Water & Wastewater,2021,37(20):53.
[8]邓娟,郑爽.排水管道水力冲洗设施在综合管廊中的应用[J].中国给水排水,2021,37(8):101.
DENG Juan,ZHENG Shuang.Application of Drainage Pipe Hydraulic Flushing Facility in the Utility Tunnel[J].China Water & Wastewater,2021,37(20):101.
[9]赵忠梁.渠县黄花大道综合管廊通风设计[J].中国给水排水,2021,37(10):79.
ZHAO Zhong-liang.Design for Ventilation of Huanghua Avenue Utility Tunnel in Qu County[J].China Water & Wastewater,2021,37(20):79.
[10]刘琳,刘勇,王树人.砂砾地层矩形截面管廊顶管施工超挖空洞消除方法[J].中国给水排水,2021,37(10):154.
LIU Lin,LIU Yong,WANG Shu-ren.An Eliminating Method of Over-excavated Holes in Pipe-jacking Construction of Utility Tunnel with Rectangular Cross-section in Gravel Stratum[J].China Water & Wastewater,2021,37(20):154.
备注/Memo
作者简介:寇殿良(1982-),男,吉林安图人,硕士,高级工程师,从事市政给排水工程设计工作。
E-mail:26482129@qq.com
收稿日期:2018-06-12