- 摘要:
- 超细干粉自动灭火装置是一种较为主流的综合管廊消防设施。国家标准未有针对超细干粉自动灭火系统的规定,而各地方标准的参数选择差距较大,因此在用于综合管廊时,超细干粉灭火系统的设计原则和细节参数无法达成广泛一致。针对上述问题,对比国家标准和各地方标准,认为在综合管廊中,超细干粉系统宜采用全淹没式超细干粉自动灭火系统;计算综合管廊超细干粉灭火剂用量时,可采用灭火剂用量=灭火剂设计浓度×容积×补偿系数的计算方法,危险等级可定义为中危险级;设计浓度和其他设计参数的选取应根据地方标准选择。
- Abstract:
- Ultra-fine dry powder fire extinguishing systems are popular fire-fighting facilities in utility tunnel now. However, the provisions of the national standard were not carried out, and the local standard parameters were quite different. So it was impossible to reach the widespread agreement on the design principles and detailed parameters for ultra-fine dry powder system fire extinguishing system in the utility tunnel. In view of these problems, with comparison of the national standards and local standards, it was considered that in utility tunnel, the ultra-fine dry powder systems should adopt fully submerged ultra-fine dry powder automatic fire extinguishing system. When calculating the dosage of ultra-fine dry powder extinguishing agent, the method of calculating dosage = the design concentration × volume × compensation coefficient could be used. Hazard level should be defined as medium hazard level. The selection of design concentration and other parameters should be based on local standards.
相似文献/References:
[1]曹益宁,董永红.城市综合管廊入廊污水管道及重要节点的设计[J].中国给水排水,2018,34(20):67.
CAO Yi ning,DONG Yong hong.Design of Sewage Pipe and Important Nodes of Urban Utility Tunnel[J].China Water & Wastewater,2018,34(22):67.
[2]寇殿良,袁建平,陈雪梅.高压细水雾灭火系统在综合管廊中的应用[J].中国给水排水,2018,34(20):72.
KOU Dian liang,YUAN Jian ping,CHEN Xue mei.Application of High-pressure Water Mist Fire Extinguishing System in Utility Tunnel[J].China Water & Wastewater,2018,34(22):72.
[3]强健.综合管廊的功能区间及应用[J].中国给水排水,2020,36(18):45.
QIANG Jian.Functional Section in the Utility Tunnel and Its Application[J].China Water & Wastewater,2020,36(22):45.
[4]唐兰,张月,王长祥.保障全周期本质安全的综合管廊规划编制方法及要求[J].中国给水排水,2020,36(24):60.
TANG Lan,ZHANG Yue,WANG Chang-xiang.Planning Compilation Methods and Technical Requirements for Utility Tunnel to Ensure Intrinsic Safety throughout the Life Cycle[J].China Water & Wastewater,2020,36(22):60.
[5]赫明水,王长祥,吕杨,等.城市综合管廊真空排水系统模型试验及设计技术研究[J].中国给水排水,2020,36(24):66.
HE Ming-shui,WANG Chang-xiang,L?Yang,et al.Research on Model Test and Design Technology about the Vacuum Drainage System of Utility Tunnel[J].China Water & Wastewater,2020,36(22):66.
[6]尚琳,刘远,何发龙,等.考虑人员安全疏散的综合管廊防火分区设计长度研究[J].中国给水排水,2020,36(24):72.
SHANG Lin,LIU Yuan,HE Fa-long,et al.Study on the Utility Tunnel Fire Compartment Design Length Considering Safe Evacuation[J].China Water & Wastewater,2020,36(22):72.
[7]许云骅,金善朝,徐浩煜.综合管廊运维目标、原则及新技术应用[J].中国给水排水,2021,37(8):53.
XU Yun-hua,JIN Shan-chao,XU Hao-yu.Targets, Principles and New Technologies Application of the Utility Tunnel Operation and Maintenance[J].China Water & Wastewater,2021,37(22):53.
[8]邓娟,郑爽.排水管道水力冲洗设施在综合管廊中的应用[J].中国给水排水,2021,37(8):101.
DENG Juan,ZHENG Shuang.Application of Drainage Pipe Hydraulic Flushing Facility in the Utility Tunnel[J].China Water & Wastewater,2021,37(22):101.
[9]赵忠梁.渠县黄花大道综合管廊通风设计[J].中国给水排水,2021,37(10):79.
ZHAO Zhong-liang.Design for Ventilation of Huanghua Avenue Utility Tunnel in Qu County[J].China Water & Wastewater,2021,37(22):79.
[10]刘琳,刘勇,王树人.砂砾地层矩形截面管廊顶管施工超挖空洞消除方法[J].中国给水排水,2021,37(10):154.
LIU Lin,LIU Yong,WANG Shu-ren.An Eliminating Method of Over-excavated Holes in Pipe-jacking Construction of Utility Tunnel with Rectangular Cross-section in Gravel Stratum[J].China Water & Wastewater,2021,37(22):154.