- Numerical Simulation of Automatic Sprinkler in High Clearance Building
- Keywords:
- high clearance building; automatic sprinkler system; numerical simulation of physical object; standard burning item; sprinkler density; response time index
- 摘要:
- 基于实体灭火试验,利用FDS数值模拟软件探究了净空高度为18 m的高大空间建筑自动喷水灭火系统不同喷水强度和响应时间指数(RTI)对灭火效果的影响。结果表明,喷水强度为30 L/(min·m2)时,自动喷水灭火系统能快速抑制火灾;喷水强度为20 L/(min·m2)时,喷头及时动作或开放多个喷头可实现控火;喷水强度为15 L/(min·m2)时,由于喷水强度较小,水滴直接送达燃料表面的量很少,但在开放更多的喷头情况下,水能有效湿润燃烧物周边的可燃物,从而有效控火。根据不同参数下的真实物品数值模拟,对喷头动作时间、启动个数、控火时间、过火面积、物品损失,以及系统的可靠性等多方面比较,提出了工程应用设计参数,建议此类场所下喷头的喷水强度为20 L/(min·m2),喷头响应类型采用快速响应。
- Abstract:
- Based on the physical fire extinguishing experiment, the effect of different sprinkler density and response time index (RTI) on fire extinguishment in a high clearance building with the clearance of 18 m was explored by using FDS numerical simulation software. When the sprinkler density was 30 L/(min·m2), the automatic sprinkler system could suppress the fire quickly and effectively. When the sprinkler density was 20 L/(min·m2), the automatic sprinkler system could act in time or open multiple sprinklers to control the fire. When the sprinkler density was 15 L/(min·m2), water droplets could not reach the fuel surface directly due to the low sprinkler density. However, when more sprinklers were opened, the water was effective in wetting the combustibles around the burner and effectively controlled the fire. According to the numerical simulation of physical objects under different parameters, operating time of sprinkler, number of opening sprinklers, fire surppression time, overfire area, fire loss and system reliability were compared, and the design parameters of engineering application were proposed.It was suggested that the sprinkler density in high clearance building should be 20 L/(min·m2), and fast response of the sprinklers should be adopted.
相似文献/References:
[1]余小明.EXCEL迭代计算在自动喷水灭火系统水力计算中的应用[J].中国给水排水,2020,36(10):41.
[2]徐得潜,钱安贞.自动喷水灭火系统设计流量计算方法的研究[J].中国给水排水,2020,36(22):130.
XU De-qian,QIAN An-zhen.Research on Calculation Method of Design Flow of Sprinkler System[J].China Water & Wastewater,2020,36(17):130.
[3]米长虹,孔德骞.自动喷水灭火系统喷头梁间优化布置探讨[J].中国给水排水,2023,39(2):80.
MIChang-hong,KONGDe-qian.Discussion on Optimal Arrangement of Sprinkler among Beams in Automatic Sprinkler System[J].China Water & Wastewater,2023,39(17):80.
更新日期/Last Update:
2020-09-01