HE Yang,YUAN Shao-chun,JIANG Bin.Design Change and Practice of Sewage Treatment Project under the Background of New Local Standards[J].China Water & Wastewater,2021,37(8):78-82.
新地方标准背景下污水处理项目的设计变更与实践
- Title:
- Design Change and Practice of Sewage Treatment Project under the Background of New Local Standards
- 摘要:
- 四川省内江市第二污水处理厂总规模为10×104 m3/d,其中一期设计规模为5×104 m3/d。根据《四川省岷江、沱江流域水污染物排放标准》(DB 51/2311—2016)的排放要求,将原设计中的预处理/改良型A2O/纤维滤池/紫外消毒组合工艺,变更为预处理/多级AO/高效沉淀池/深床反硝化滤池/次氯酸钠接触消毒组合工艺,并利用WEST软件对多级AO除磷脱氮工艺建立仿真模型,取得了较优的运行参数。工程实践结果表明,对TN、SS、TP、COD、NH3-N、BOD5的去除率分别达到81.8%、98.3%、94.8%、91.1%、97.3%、93.3%,出水水质符合地方排放标准的要求。本工程适时进行设计变更,有效避免了投资上的浪费。
- Abstract:
- The total treatment capacity of the Neijiang second sewage treatment plant in Sichuan Province is 10×104 m3/d, and the design treatment capacity of the first phase is 5×104 m3/d. According to discharge requirements of Minjiang River and Tuojiang River Basin Water Pollution Discharge Standards of Sichuan Province (DB 51/2311-2016), the original combined process consisting of pretreatment, modified A2O, fiber filter and UV disinfection was changed into pretreatment, multi-stage AO, high efficiency sedimentation tank, deep bed denitrification filter and sodium hypochlorite contact disinfection. A simulation model of multi-stage AO dephosphorization and denitrification process was established by using WEST software, and optimal operational parameters were obtained. The removal efficiencies of TN, SS, TP, COD, NH3-N and BOD5 reached 81.8%, 98.3%, 94.8%, 91.1%, 97.3% and 93.3%, respectively, and the effluent quality met the discharge requirements of local standards. Design of the project was changed in time, which effectively avoided the waste of investment.
相似文献/References:
[1]谢晓旺.多级AO与氧化沟工艺在污水厂扩建工程中应用对比[J].中国给水排水,2020,36(14):127.
XIE Xiao-wang.Application Comparison of Multi-stage AO and Oxidation Ditch Process in a WWTP Expansion Project[J].China Water & Wastewater,2020,36(8):127.
[2]杨清,郭淑琴,陈伟楠.准Ⅳ类出水标准下天津咸阳路污水处理厂的迁建提标设计[J].中国给水排水,2021,37(12):88.
YANG Qing,GUO Shu-qin,CHEN Wei-nan.Design of Relocation of Tianjin Xianyanglu Sewage Treatment Plant Upgraded to Quasi-Ⅳ Standard[J].China Water & Wastewater,2021,37(8):88.
[3]刘增军,张开海,孙序营,等.多级AO用于高排放标准下低碳高氮生活污水处理[J].中国给水排水,2024,40(2):55.