[1]倪亭亭,王云钟,吴永明,等.湿法烟气脱硫废水处理工程实例[J].中国给水排水,2022,38(4):109-113.
NITing-ting,WANGYun-zhong,WUYong-ming,et al.Case of Wet Flue Gas Desulfurization Wastewater Treatment Project[J].China Water & Wastewater,2022,38(4):109-113.
点击复制
NITing-ting,WANGYun-zhong,WUYong-ming,et al.Case of Wet Flue Gas Desulfurization Wastewater Treatment Project[J].China Water & Wastewater,2022,38(4):109-113.
湿法烟气脱硫废水处理工程实例
中国给水排水[ISSN:1000-4062/CN:12-1073/TU]
卷:
第38卷
期数:
2022年第4期
页码:
109-113
栏目:
出版日期:
2022-02-17
- Title:
- Case of Wet Flue Gas Desulfurization Wastewater Treatment Project
- Keywords:
- desulfurization wastewater; wet limestone-gypsum; chemical precipitation method; coagulation sedimentation
- 摘要:
- 针对某热电厂石灰石-石膏法烟气脱硫工艺废渣处理系统产生的脱硫废水,采用化学沉淀工艺进行处理,经过一年的运行发现其技术可靠、稳定,对悬浮物、COD、氟化物、汞、硫酸盐的去除率分别达到99.5%、98.3%、87.5%、99.8%、85.6%,对应出水浓度分别为54、20、9.6、0.04、980 mg/L,出水水质满足并优于《火电厂石灰石-石膏湿法脱硫废水水质控制指标》(DL/T 997—2006)的要求,且电费和药剂费合计仅为6.65 元/m3。
- Abstract:
- The desulfurization wastewater generated by the waste residue treatment system of the limestone-gypsum flue gas desulfurization (FGD) process in a thermal power plant is treated by chemical precipitation process. After one year of operation, the technology is found reliable and stable. The removal rates of SS, COD, fluoride, mercury and sulfate reached 99.5%, 98.3%, 87.5%, 99.8% and 85.6% respectively, and the corresponding effluent concentrations were 54 mg/L, 20 mg/L and 9.6 mg/L, 0.04 mg/L, 980 mg/L. Finally, the effluent quality of the system is no less than the requirements of Discharge Standard of Wastewater from Limestone?gypsum Flue Gas Desulfurization System in Fossil Fuel Power Plants (DL/T 997-2006). In addition, the total cost of electricity and chemical is only 6.65 yuan/m3.
相似文献/References:
[1]周明飞,连坤宙,王璟,等.电渗析技术处理脱硫废水的效果分析[J].中国给水排水,2020,36(21):80.
ZHOU Ming-fei,LIAN Kun-zhou,WANG Jing,et al.Efficiency Analysis of Desulfurization Wastewater Treated by Electrodialysis Technology[J].China Water & Wastewater,2020,36(4):80.
[2]陈丽娜,尤良洲,韩倩倩,等.燃煤电厂全厂废水零排放改造工程设计及运行效果[J].中国给水排水,2023,39(20):132.
CHEN Li-na,YOULiang-zhou,HANQian-qian,et al.Design and Operation Effect of a Wastewater Zero Discharge Reconstruction Project in Coal-fired Power Plant[J].China Water & Wastewater,2023,39(4):132.
更新日期/Last Update:
2022-02-17