低温条件下微孔曝气氧化沟中试装置的调试及启动
- Title:
- Commissioning and Start-up of Pilot-scale Microporous Oxidation Ditch at Low Temperature
- Keywords:
- microporous aeration oxidation ditch; low temperature; start-up; nitrogen and phosphorus removal
- 摘要:
- 采用微孔曝气氧化沟中试装置处理实际污水处理厂沉砂池出水,研究了中试装置在低温条件下实现启动的可行性和可靠性。结果表明,中试装置抗冲击负荷能力较强,在低温条件下(13~18 ℃),控制好氧区DO浓度为0.5~1.0 mg/L,系统运行稳定;试验后期,中试装置出水指标除TP外其余均满足《城镇污水处理厂污染物排放标准》一级A标准要求。因此,在低温条件下中试装置可通过降低系统曝气量实现启动。分析了除磷效果不佳的原因,主要与排泥不规律、接种污泥除磷能力较差、回流污泥中含有硝态氮等有关。
- Abstract:
- A pilot-scale microporous aeration oxidation ditch was applied to treat the effluent from a grit chamber of a wastewater treatment plant, and the feasibility and reliability of starting up the pilot plant at low temperature were investigated. The pilot plant had strong shock load resistance, and the system operated stably at low temperatures between 13 ℃ to 18 ℃ when maintaining dissolved oxygen concentration between 0.5 mg/L and 1.0 mg/L. Except TP, the effluent quality of the pilot plant reached the first level A criteria of Discharge Standard of Pollutants for Municipal Wastewater Treatment Plant during the late period of the test. The pilot plant could be started up by reducing the aeration rate at low temperature. The reason for poor phosphorus removal was mainly related to irregular sludge discharge,poor phosphorus removal capacity of inoculated sludge and nitrate in the reflux sludge.
相似文献/References:
[1]韩懿,张建兵,黄巍,等.曝停比对低温单级自养脱氮系统效能影响研究[J].中国给水排水,2018,34(21):70.
HAN Yi,ZHANG Jian bing,HUANG Wei,et al.Effect of Aeration/Idle Time Ratio on Single stage Autotrophic Nitrogen Removal System at Low Temperature[J].China Water & Wastewater,2018,34(7):70.
[2]刘强,王泰,沈浡,等.MBBR工艺用于污水厂提标改造的低温运行效果[J].中国给水排水,2020,36(13):7.
LIU Qiang,WANG Tai,SHEN Bo,et al. Operation Effect of MBBR Applied in Upgrading and Reconstruction of a Wastewater Treatment Plant in Tianjin at Low Temperature [J].China Water & Wastewater,2020,36(7):7.
[3]郝桂珍,范宇成,徐利,等.低温下好氧颗粒污泥强化造粒研究[J].中国给水排水,2020,36(19):32.
HAO Gui-zhen,FAN Yu-cheng,XU Li,et al.Enhanced Granulation of Aerobic Granular Sludge at Low Temperature[J].China Water & Wastewater,2020,36(7):32.
[4]杨红,白文龙,梅小乐,等.寒冷地区冬季脱氮除磷工艺调控及效果分析[J].中国给水排水,2021,37(6):107.
YANG Hong,BAI Wen-long,MEI Xiao-le,et al.Adjustment and Analysis of Nitrogen and Phosphorus Removal Process to Resist Winter in Cold Regions[J].China Water & Wastewater,2021,37(7):107.
[5]茹春,张爽,路晖,等.低温条件下污水处理厂的除污效果及运行调控分析[J].中国给水排水,2021,37(9):1.
RU Chun,ZHANG Shuang,LU Hui,et al.Pollutants Removal Performance and Operation Regulation of Urban Wastewater Treatment Plant under Low Temperature Condition[J].China Water & Wastewater,2021,37(7):1.
[6]周家中,宋平周,张爽,等.占地受限下北方某高标准新建污水厂工程设计[J].中国给水排水,2021,37(12):76.
ZHOU Jia-zhong,SONG Ping-zhou,ZHANG Shuang,et al.Engineering Design of a New High-standard Wastewater Treatment Plant with Limited Footprint Area in North China[J].China Water & Wastewater,2021,37(7):76.
[7]李伟光,吕龙义,金佳林,等.两级生物强化过滤处理低温微污染地下水中试研究[J].中国给水排水,2021,37(21):26.
LI Wei-guang,Lü Long-yi,JIN Jia-lin,et al.Pilot-scale Study on Treatment of Low-temperature and Micro-polluted Groundwater by Two-stage Bio-enhanced Filtration[J].China Water & Wastewater,2021,37(7):26.
[8]于莉芳,莫鹏程,杨秀玲,等.长期运行条件下亚硝酸盐氧化菌的低温适应策略[J].中国给水排水,2021,37(23):68.
YU Li-fang,MO Peng-cheng,YANG Xiu-ling,et al.Strategy for Nitrite Oxidizing Bacteria Adapting to Low Temperature during Long-term Operation[J].China Water & Wastewater,2021,37(7):68.